I have never used the data fanout, so I don't know about it. For the
requirement you described I would use two sequence (seq) records (each
has ten output links with a unique data source link (DOLn) for each).
Make all the data source links (DOLn) indentical and it becomes a data fanout.
Ned
>
> Hi All:
>
> According to the Record Reference Manual, a Fanout record which supports six
> output links, can be chained with one or more additional Fanout records in
order
> to increase the number of output links available. For example, two Fanouts
> records chained together can propagate 11 outputs (one output from the first
> record links to the input of the second).
>
> The Data Fanout record is "similar" to the Fanout. Where as the Fanout record
> only supports control links (i.e. no data is passed), the Data Fanout
propagates
> control AND data. A Data Fanout record supports eight output links. Can the
Data
> Fanout record also be chained, like the Fanout? If so, could someone explain
> how? I have tried every permutation I can thank of, linking various types of
> records with the Data Fanout, to no avail.
>
> My needs are a Data Fanout of 16 outputs from a single Binary Output. I have
> successfully used a single Data Fanout with all eight outputs.
>
> Thanks
> Russ
- Replies:
- Re: Data Fanouts Maren Purves
- Navigate by Date:
- Prev:
Data Fanouts Russell Page
- Next:
Re: Data Fanouts Maren Purves
- Index:
1994
1995
1996
1997
1998
1999
<2000>
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
Data Fanouts Russell Page
- Next:
Re: Data Fanouts Maren Purves
- Index:
1994
1995
1996
1997
1998
1999
<2000>
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
|