g+
g+ Communities
Argonne National Laboratory

Experimental Physics and
Industrial Control System

1994  <19951996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  Index 1994  <19951996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013 
<== Date ==> <== Thread ==>

Subject: Re: edd/dm
From: dalesio@luke.atdiv.lanl.gov (Bob Dalesio)
To: tech-talk@aps.anl.gov
Date: Fri, 13 Oct 95 10:07:17 MDT
The stripcharts have a major stupidity in them -
they only update when monitors come back. So,
for those variables - set the MDEL field to -1
and it will send monitors on each scan.
This is slated for re-write and unfunded. Let me
know if you are interested.

Loosing contact - I don't understand. Could you
elaborate? Also - what version?

	Thanks,
	Bob