Pump Rounds - Secondary Systems

SECONDARY SYSTEMSVAC SKID
PUMP
NUMBER
JCI
NAME
A-B TEMP
(degf)
DP
(psi)
PWS-F
(gpm)
PWR-F
(gpm)
BYPASS
(% closed)
DISCH
(psi)
OILMAG
(ohms)
VFDFILT D.P.
(psi)
A-B TEMP
(degf)
MAG
(ohms)
FILT D.P.
DI H20
FILT D.P.
CH W
UV
Light
WATER
LEVEL
DATE/TIME
PW SEG 1P-SRVC-04A/B
P-501/502PSR04A-B78.0101358360100144OkOk37815.420On22016-07-27 14:21:50
PW SEG 2P-SRVC-06A/B
P-503/504PSR06A-B78.0105400400100135Ok10.2Ok37816.114On02016-07-27 14:21:50
PW SEG 3P-SRVC-08A/B
P-505/506 PSR08A-B78.0108358353100160OkOk37817.020On42016-07-27 14:21:50
PW SEG 4P-SRVC-10A/B
P-507/508PSR10A-B78.0102364370100130OkOk37817.010On32016-07-27 14:21:50
PW SEG 5P-SRVC-12A/B
P-509/510PSR12A-B78.0105376376100142OkOk67817.212On12016-07-27 14:21:50
PW SEG 6P-SRVC-14A/B
P-511/512PSR14A-B78.0103345336100159OkOk27816.501On12016-07-27 14:21:50
PW SEG 7P-SRVC-16A/B
P-513/514PSR16A-B78.0108410429100162OkOk57816.810On02016-07-27 14:21:50
PW SEG 8P-SRVC-18A/B
P-515/516PSR18A-B78.0107371381100125OkOk27817.014On32016-07-27 14:21:50
PW SEG 9P-SRVC-20A/B
P-517/518PSR20A-B78.0105354363100144OkOk47816.710On32016-07-27 14:21:50
PW SEG 10P-SRVC-22A/B
P-519/520PSR22A-B78.0102348359100153OkOk27815.913On02016-07-27 14:21:50
PW SEG 11P-SRVC-24A/B
P-521/522PSR24A-B78.0103393399100145OkOk27815.913Off02016-07-27 14:21:50
PW SEG 12P-SRVC-26A/B
P-523/524PSR26A-B78.099.7324321100153Ok9.87Ok37817.205Off02016-07-27 14:21:50
PW SEG 13P-SRVC-28A/B
P-525/526PSR28A-B78.0101328334100144OkOk37815.130On32016-07-27 14:21:50
PW SEG 14P-SRVC-30A/B
P-527/528PSR30A-B78.0113356359100153OkOk77816.422On02016-07-27 14:21:50
PW SEG 15P-SRVC-32A/B
P-529/530PSR32A-B78.0101355363100136OkOk37816.412On02016-07-27 14:21:50
PW SEG 16P-SRVC-34A/B
P-531/532PSR34A-B78.0106341337100143OkOk67817.910On22016-07-27 14:21:50
PW SEG 17P-SRVC-36A/B
P-533/534PSR36A-B78.098.4408409100141OkOk47816.323On12016-07-27 14:21:50
PW SEG 18P-SRVC-38A/B
P-535/536PSR38A-B78.0106287286100162OkOk87817.820Off12016-07-27 14:21:50
RING WESTP-SRVC-40A/B
P-401/402PSR40A-B78.0107276277100156OkOk07813.83OOn22016-07-27 14:21:50
RING EASTP-SRVC-02A/B
P-404/405PSR02A-B78.0102354383100141OkOk57816.514On02016-07-27 14:21:50
PUMP
 NUMBER 
JCI
   NAME   
A-B TEMP
(degf)
DP
(psi)
PWS-F
(gpm)
PWR-F
(gpm)
BYPASS
(% closed)
DISCH
  (psi)  
OILMAG
(ohms)
VFDFILT D.P.
(psi)
DATE/TIME
EAA
P-403PSREAA78.094.8107107100138OkOk32016-07-27 14:21:50
SPX
P-SPX 78.070.044.644.366.8101Ok67.82016-07-27 14:21:50
NAMECOMMENTSDATE/TIME
Bob Furst2016-07-27 14:21:50

Pump Rounds - RF/LINAC/INJECTION

PUMP
NUMBER
SERVICEA-B TEMP
(degf)
SET POINT TEMP
(degf)
PWS-F
(gpm)
PWR-F
(gpm)
D.P.BYPASS
(% closed)
DISCH
(psi)
OILMAG
(ohms)
VFDFILT D.P.
(psi)
DATE/TIME
BLDG. 411/412
P-101TUNNEL89.99010310189100120OkOk02016-07-27 08:14:19
P-102GALLERY89.990288290580122OkOk12016-07-27 08:14:19
P-103STANDBY0.002016-07-27 08:14:19
P-201PAR (INJ)80.08042042578100116OkOk52016-07-27 08:14:19
P-301ST. SOUTH90.090387387106100116OkOk22016-07-27 08:14:19
P-302STANDBY0.002016-07-27 08:14:19
LEUTLLEUTL0.002016-07-27 08:14:19
P-PR-MOD1MODULATORS0.002016-07-27 08:14:19
P-PR-MOD2MODULATORS0.06522016-07-27 08:14:19

DISSOLVED
OXYGEN
MAG
(ohms)
DATE/TIME
D.O.2.62016-07-27 08:14:19
RESISTIVITY10.12016-07-27 08:14:19

PUMP
NUMBER
SERVICEA-B TEMP
(degf)
SET POINT TEMP
(degf)
PWS-F
(gpm)
PWR-F
(gpm)
D.P.BYPASS
(% closed)
DISCH
(psi)
OILMAG
(ohms)
VFDFILT D.P.
(psi)
DATE/TIME
BLDG. 420
P-901RF-185.98654353695100128Ok10.2Ok62016-07-27 08:14:19
P-902RF-284.98550450697100128OkOk62016-07-27 08:14:19
P-303ST. NORTH89.990405476111100148OkOk4.52016-07-27 08:14:19
P-903STANDBY0.002016-07-27 08:14:19
P-910RF-TS180.0805205272970190Ok42016-07-27 08:14:19
P-904STANDBY0.002016-07-27 08:14:19
P-905RF-585.08554153994100120OkOk52016-07-27 08:14:19
P-906RF-388.98552952289100132OkOk62016-07-27 08:14:19
P-907RF-485.08948548993100140OkOk52016-07-27 08:14:19
P-908RF LOADS85.085392377111100126OkOk32016-07-27 08:14:19
P-909STANDBY 0.002016-07-27 08:14:19

NAMECOMMENTSDATE/TIME
John Dench2016-07-27 08:14:19